ProductProduct display
HEX-150 Heat Exchanger
1. Enclosed air circuit cooling system design, which make the inside air and outside air isolated and effectively avoid contamination from outside.
2. Avoid dew formation from too cold.
3. Compact structure and convenient installation & maintenance.
4. It can be remote monitored.
5. Voltage range: AC220v, 50Hz/60Hz; AC110v, 60Hz; DC-48V.
6. The main components are international brand which greatly improves the reliability of the system.
Plate heat exchanger is a device that introduces outdoor natural cold source to exchange heat with limited power consumption. When there is a large temperature difference, the device will effectively exchange heat between hot air inside and cool air outside the cabinet through the aisle of multilayer aluminum heat sink fins, which make the cabinet be an enclosed system with constant temperature so that equipment inside the cabinet can work normally.
Model | Heat Transfer (W/K) | Rated Voltage (V/ph/Hz) | Rated Power (W) | Air Circuit (m³/h) | HxWxD (mm) | Weight (Kgs) |
HEX-50 | 50 | 220/1/50 | 40 | 400 | 750x411x118 | 20 |
HEX-60 | 60 | 220/1/50 | 50 | 500 | 750x411x118 | 20 |
HEX-80 | 80 | 220/1/50 | 60 | 800 | 1177x410x154 | 25 |
HEX-100 | 100 | 220/1/50 | 150 | 900 | 1177x410x154 | 25 |
HEX-120 | 120 | 220/1/50 | 185 | 1100 | 1237x410x154 | 28 |
HEX-150 | 150 | 220/1/50 | 220 | 1300 | 1358x555x195 | 34 |
HEX-200 | 200 | 220/1/50 | 260 | 2000 | 1520x600x198 | 38 |
1. Outdoor telecom cabinet
2. Outdoor battery cabinet
3. Electrical cabinet
4. Industrial control cabinet